'Specifications_without_split': 'Production Products: 1. The range of measured vibroscency, SKZ: 200 mm/s. The operating frequency range (uneven frequency response ± 3 dB): 2 ... 1,000 Hz. The range of operating frequencies of the measured vibration rushing (uneven Farm Code ± 3 dB): 10 ... 1,000 Hz. Range of operating temperatures: - 40 ... + 70 ° C. Type of input connectors: screw terminals. The measurement error in the working temperature range: ± 2 %. Types of connected vibration transformers: IEPE, 4-20 Ma, RS-485 (up to 8 pcs.). Types of input signals: 0-10 V, 4-20 Ma, RS-485. Data exchange: RS485. Sensor supply voltage: IEPE, 4-20 MA: 24 ± 2 V. The sensors power voltage: RS-485: 5 ± 0.5 V. The power current IEPE sensors (± 10 %): 5.7 mA. Dry contacts: to control vibro: AL1, AL2. Dry contacts: To control the connected sensor: OK. The step of the operation thresholds: 0.1 (1) mm/s. The conditions for issuing signals (closed or open) contacts of the relay "AL1", "AL2": continuous excess with an informative signal of a given threshold value within 0-9 s. The step of setting the time for the excess of threshold values of vibration rushing: 1 p. Relay contacts operation mode: blocking/ self -healing. The condition of self -healing: a decrease in vibration from the threshold of the operation by 6%. The delay in vibration control after the establishment of the working regime/ self -healing: 0 or 20. The parameters of the “dry” contact: constant switching current: & lt; 1 A. The parameters of “dry” contact: & lt voltage: & lt; 30 V. Information displayed on the built -in indicator: SKZ: SKZ vibration ranges, coefficient of transformation of the sensor, the values of the specified thresholds, errors in the cable break and failure of the sensor, setting the time for excess of threshold values, the state of relay contacts. Power (voltage): 24 B. Power (current): & lt; 200 mA. Fastening on DIN - Reiku: Yes. Mass: 200 g '}